System Losses

The system losses account for performance losses you would expect in a real system that are not explicitly calculated by the PVWatts® model equations.

The default value for the system losses of 14% is based on the categories in the table below, and calculated as follows:

100% × [ 1- ( 1 - 0.02 ) × ( 1 - 0.03 ) ×
( 1 - 0.02 ) × ( 1 - 0.02 ) ×
( 1 - 0.005 ) × ( 1 - 0.015) ×
( 1- 0.01 ) × ( 1 - 0.03) ] = 14%

The Inverter's DC-to-AC Conversion Efficiency is a separate input under Advanced Parameters with a default value of 96%. Do not include inverter conversion losses in the system loss percentage.

PVWatts® calculates temperature-related losses as a function of the cell temperature, so you should not include temperature loss in the system loss percentage. See the Technical Reference for details.

If you want to use a value other than the default, you can either type a new value, or use the calculator specify values for the categories listed in the table below. For a description of the categories, see System Losses Categories.

Default values for the system loss categories
Category Default Value (%)
Soiling 2
Shading 3
Snow 0
Mismatch 2
Wiring 2
Connections0.5
Light-Induced Degradation 1.5
Nameplate Rating 1
Age 0
Availability3